1. المقدمة وما فوقview
The APC AP7921 is a Switched Rack Power Distribution Unit (PDU) designed for efficient power management in rack environments. This 1U horizontal mounting PDU provides eight (8) C13 output receptacles and accepts a 208V-230V input via an IEC-320 C20 connector, supporting a 16A single-phase load. It offers advanced features such as remote individual outlet control, local current monitoring, and remote management capabilities, making it suitable for critical IT infrastructure.

الشكل 1.1: الجبهة view of the APC AP7921 Switched Rack PDU, showing the eight C13 output receptacles and the local current monitoring display.
المميزات الرئيسية:
- 1U Horizontal Mounting: Designed for easy integration into standard server racks.
- منافذ التبديل: Remote individual control of eight (8) C13 output receptacles.
- طاقة الإدخال: IEC-320 C20 connector for 208V-230V, 16A single-phase input (3.3 kW).
- Local Current Monitoring: Integrated display for real-time current monitoring.
- الإدارة عن بعد: Capabilities for remote current monitoring, outlet control, and configuration.
- Flash Upgradeable: Supports firmware updates for enhanced functionality.
- حدود التنبيه: Configurable thresholds for power events.
- Power Delays: Sequential power-up/down capabilities for connected equipment.
2. معلومات السلامة
Read and understand all instructions before installing or operating this equipment. Failure to follow these instructions may result in electric shock, fire, or serious injury.
- PDU هذا مخصص للاستخدام الداخلي فقط.
- Connect the PDU to a properly grounded power source.
- Do not attempt to open or service the PDU. There are no user-serviceable parts inside.
- Ensure that the total current draw of connected equipment does not exceed the PDU's maximum rated current (16A).
- Use only appropriate power cords for connecting devices to the PDU outlets.
- Keep liquids away from the PDU.
3. محتويات العبوة
Verify that all components are present upon unpacking. If any items are missing or damaged, contact your vendor or APC support.
- APC AP7921 Switched Rack PDU
- Rack mounting hardware (brackets, screws)
- التوثيق (دليل البدء السريع، معلومات السلامة)
- Serial configuration cable (if applicable)
4. الإعداد والتثبيت
4.1 تركيب الرف
- Identify a 1U (1.75 inches) space in your standard 19-inch server rack.
- Attach the provided mounting brackets to the sides of the PDU using the included screws.
- Secure the PDU into the rack using appropriate rack screws, ensuring it is firmly seated.
4.2 توصيل الطاقة
- Connect the IEC-320 C20 input connector of the PDU to a compatible 208V-230V, 16A power source. Ensure the power source is properly grounded and capable of supplying the required current.
- Connect your IT equipment's power cords to the eight (8) C13 output receptacles on the PDU. Distribute the load evenly across the outlets if possible.
5. التشغيل
5.1 التشغيل
Once the PDU is connected to a power source, it will power on automatically. The local current monitoring display will illuminate, showing the total current draw.
5.2 Local Current Monitoring
The integrated display on the front panel provides real-time information on the total current being drawn by all connected devices. This helps in preventing overloads and managing power capacity.
5.3 Remote Individual Outlet Control
The AP7921 allows for remote control of each individual C13 outlet. This feature enables users to power cycle, turn on, or turn off connected equipment remotely, which is beneficial for troubleshooting or managing power to specific devices without physical access.
5.4 Power Delays
The PDU supports configurable power-on and power-off delays for its outlets. This feature helps in sequencing the startup of equipment to prevent inrush current overloads and manage system dependencies.
6. التكوين
The AP7921 PDU offers various configuration options through its network interface for remote management.
6.1 الوصول إلى الشبكة
Connect the PDU to your network using an Ethernet cable. Access the PDU's web interface via its assigned IP address to configure settings, monitor status, and control outlets. Refer to the network configuration guide for initial setup.
6.2 Alarm Thresholds
Configure alarm thresholds for current draw. The PDU can send alerts via email or SNMP traps if the current exceeds or falls below specified limits, helping to prevent overloads or identify power issues.
6.3 تحديثات البرامج الثابتة
The PDU's firmware is flash upgradeable. Regularly check the APC website for the latest firmware versions to ensure optimal performance and access to new features. Follow the provided instructions for firmware upgrade procedures.
7. الصيانة
7.1 التنظيف
Periodically clean the exterior of the PDU with a soft, dry cloth. Do not use liquid cleaners or solvents. Ensure the PDU is disconnected from the power source before cleaning.
7.2 الاعتبارات البيئية
Ensure the PDU operates within its specified temperature and humidity ranges. Maintain proper airflow around the unit to prevent overheating.
8. استكشاف الأخطاء وإصلاحها
8.1 No Power to Outlets
- Verify the input power cable is securely connected to both the PDU and the power source.
- Check the circuit breaker on the PDU (if present) and the upstream circuit breaker.
- Ensure individual outlets are not remotely switched off.
8.2 Overload Indication
- If the local display or remote interface indicates an overload, immediately disconnect non-essential equipment.
- Reduce the total load to below the PDU's maximum rated current (16A).
- Check for short circuits in connected equipment.
8.3 مشاكل الوصول عن بعد
- Verify network cable connection and network status.
- Confirm the PDU's IP address and network settings.
- Ensure firewall rules are not blocking access to the PDU's management interface.
9. المواصفات
| ميزة | مواصفة |
|---|---|
| رقم الموديل | AP7921 |
| حجم الإدخالtage | 208 فولت-230 فولت |
| تيار الإدخال | 16 أمبير |
| موصل الإدخال | IEC-320 C20 |
| أوعية الإخراج | 8 x IEC-320 C13 |
| عامل الشكل | 1U Horizontal Rack-Mountable |
| أبعاد المنتج (الارتفاع × العرض × العمق) | 2.7 × 18.5 × 13.5 بوصة (تقريبًا) |
| وزن العنصر | 1.54 رطل |
| طول السلك | 7.8 بوصة |
| ميزة خاصة | Mountable, Switched Outlets, Remote Management |
| الشركة المصنعة | مؤتمر القمة العربي |
10. الضمان والدعم
For warranty information, technical support, or service inquiries, please refer to the official APC website or contact your local APC representative. Ensure you have your product model number (AP7921) and serial number available when contacting support.
الموارد المتاحة على الإنترنت: يزور www.apc.com for product documentation, software downloads, and support contact information.