GODIYMODULES Standard Edition

GODIYMODULES Digital Display Meter Standard Edition User Manual

Model: Standard Edition

1. المقدمة

This manual provides comprehensive instructions for the installation, operation, and maintenance of the GODIYMODULES Digital Display Meter, Standard Edition. This universal analog input display meter is designed to work with various sensors that provide analog output, such as temperature transmitters, frequency converters, motor speed sensors, pressure transducers, and liquid level sensors. Please read this manual thoroughly before operating the device to ensure correct usage and optimal performance.

2. انتهى المنتجview

The GODIYMODULES Digital Display Meter is a versatile panel meter capable of displaying actual physical quantities based on analog input signals. It supports both current and voltage inputs, with default adaptations for 0-10V, 2-10V, 0-20mA, and 4-20mA. The meter features a 0.55-inch 4-digit digital tube display for clear readings and intuitive button controls for parameter settings.

أمام view of the GODIYMODULES Digital Display Meter

الشكل 2.1: أمام view of the GODIYMODULES Digital Display Meter, showing the digital display and control buttons.

3. الميزات الرئيسية

  • Universal Analog Input: Compatible with 0-10V, 2-10V, 0-20mA, and 4-20mA signals. Adaptable to other ranges via polarization and gain parameters.
  • نطاق واسع لإمدادات الطاقة: DC6~25V for standard and RS485 versions; DC8~25V for relay output version.
  • حماية الطاقة: Features anti-reverse connection and surge protection.
  • Single Analog Input: Supports either voltagه أو المدخلات الحالية.
  • معاوقة الإدخال: >30kΩ for voltage type, <250Ω for current type.
  • عرض واضح: 0.55 inch, 4-digit digital tube display.
  • Easy Parameter Setting: Built-in buttons for convenient configuration.
  • تصميم مضغوط: Mechanical size of 79 x 43 x 25 mm, with an installation opening of 76.5 x 39.5 mm.
  • Optional RS485 Interface: (Available in RS485 version) Supports Modbus-RTU protocol for multi-meter communication.
  • Optional Relay Output: (Available in relay output version) One normally open relay output, load capacity: 3A30VDC/3A250VAC.

4. الإعداد

4.1. التركيب الميكانيكي

The meter is designed for panel mounting. Ensure the installation opening in your panel matches the specified dimensions.

  • الحجم الميكانيكي: 79 mm (Length) x 43 mm (Width) x 25 mm (Depth)
  • افتتاح التثبيت: 76.5 mm (Length) x 39.5 mm (Width)
زاوية علوية view of the meter showing buttons and terminal block

الشكل 4.1: زاوية علوية view of the meter, illustrating the physical form factor and button layout.

بزاوية view of the meter showing buttons and terminal block from another perspective

الشكل 4.2: زاوية أخرى view of the meter, providing a clearer look at the control buttons and terminal block.

4.2. تعليمات الأسلاك

Refer to the common wiring diagram for proper connection of power supply and analog input. Ensure the power supply voltagيقع حرف e ضمن النطاق المحدد لمنع حدوث الضرر.

خلف view of the meter with wiring diagram and terminal labels

الشكل 4.3: خلف view of the meter showing the wiring diagram for power, ground, and analog input terminals.

أوصاف المحطة:

  • PWR: Positive power supply input (DC6~25V for standard/RS485, DC8~25V for relay version).
  • أرض الواقع: Ground connection for power supply and analog input.
  • الذكاء الاصطناعي: التناظرية المجلدtage Input (0-10V, 2-10V).
  • مللي أمبير: Analog Current Input (0-20mA, 4-20mA).
  • نورث كارولاينا: Not Connected.
  • RS485 (R, T, S): For RS485 communication (available in RS485 version only). R indicates data reception, T indicates data transmission, S indicates signal ground.
  • Relay (NO): Normally Open relay output (available in relay output version only).

مهم: The meter supports either voltage input (AI) or current input (mA), but not both simultaneously. Connect your sensor output to the appropriate terminal.

5. تعليمات التشغيل

5.1. Button Functions and Display States

The meter features four buttons for navigation and parameter adjustment: SET, UP (↑), DOWN (↓), and OK. The 4-digit digital display shows the measured value or parameter settings.

وظائف الأزرار:

  • جلس: Enters parameter setting mode or cycles through parameter groups.
  • UP (↑): Increases value or navigates up in menus.
  • DOWN (↓): Decreases value or navigates down in menus.
  • OK: Confirms selection or saves parameter changes.

Digital Tube Display State Transition Diagram:

The meter typically displays the measured value. Pressing the SET button allows entry into the parameter setting menu. Use UP/DOWN to navigate and OK to select/confirm. Pressing SET again will exit the parameter setting mode or move to the next parameter group.

5.2. إعدادات المعلمة

The meter's functionality is configured through various parameters organized into groups. To enter the parameter setting mode, press the تعيين الزر. استخدم UP و تحت أزرار لضبط القيم و OK للتأكيد اضغط تعيين to move between parameters or exit.

5.2.1. F0-0 Displayed Quantity Collection Parameters

المعلمةScope and Descriptionالإعدادات الافتراضيةقراءة/كتابة
ف0-0Displayed value monitoring: Displays the current collected value. Range: 0-100.0%0.0للقراءة فقط
ف0-1Display accuracy: The number of decimal places displayed in the collected value. Range: 0-31قراءة/كتابة
ف0-2Show minimum: The minimum value corresponding to "acquisition value" 0%. Range: -9999 to 99990قراءة/كتابة
ف0-3Show maximum: The maximum value corresponding to the "acquisition value" is 100%. Range: -9999 to 99991000قراءة/كتابة
ف0-4Display range: The display range is F0-2 to F0-3. Starting from F0-2.0قراءة/كتابة

ملحوظة: The displayed value is a default percentage. You can set your own display range using F0-2 to F0-4.

5.2.2. F1-0 Parameter Group Configuration Parameters

المعلمةScope and Descriptionالإعدادات الافتراضيةقراءة/كتابة
ف1-0Input type selection: 0: 0-10V or 0-20mA (corresponds to 0-100% of the acquisition value). 1: 2-10V or 4-20mA (corresponds to 0-100% of the acquisition value).0قراءة/كتابة
ف1-1Input filter time: The filtering time for the input signal. Range: 0-1000ms.200قراءة/كتابة
ف1-2Input offset: The offset value for the input signal. Range: 0-100.0%0.0قراءة/كتابة
ف1-3Input gain: The gain value for the input signal. Range: 0-100.0%100.0قراءة/كتابة
ف1-4Drop detection threshold: If the input value is not detected, the display will show "----". This parameter sets the threshold for detection. If the input value is less than this threshold, it is considered not detected. Range: 0-100.0% (Starting from V0.10)0.0قراءة/كتابة

ملحوظة: By setting the polarization parameter (F1-2) and gain parameter (F1-3), the meter can be adapted to other input ranges within 0-10V or 0-20mA.

5.2.3. F2-0 Parameter Group Relay Output Parameters (for Relay Output Version)

المعلمةScope and Descriptionالإعدادات الافتراضيةقراءة/كتابة
ف2-0Relay output: 0: Normally open, 1: Normally closed.0قراءة/كتابة
ف2-1Condition type: 0: Greater than comparison value 1, 1: Less than comparison value 1, 2: Greater than comparison value 2, 3: Less than comparison value 2.0قراءة/كتابة
ف2-2Comparison value 1: The value used for comparison. Range: 0-100.0%50.0قراءة/كتابة
ف2-3Comparison value 2: The value used for comparison. Range: 0-100.0%0.0قراءة/كتابة
ف2-4Hysteresis interval: The hysteresis value to prevent frequent relay operation. Range: 0-100.0%5.0قراءة/كتابة
ف2-5Relay status when offline: 0: Keep current status, 1: When the offline value is less than the comparison value, the relay is closed, 2: When the offline value is greater than the comparison value, the relay is closed.0قراءة/كتابة

ملحوظة: These parameters are only applicable to the version of the meter equipped with a relay output. The Standard Edition may not include this feature.

5.3. RS485 Communication Parameters (for RS485 Version)

This section applies only to the Digital Display Meter with RS485 interface. It uses the standard Modbus-RTU protocol for communication.

Detailed diagram showing parameter settings for F0, F1, F2, and RS485 communication

الشكل 5.1: Comprehensive parameter tables including F0, F1, F2, and RS485 communication settings.

المعلمةScope and Descriptionالإعدادات الافتراضيةقراءة/كتابة
ف7-0Local address: The address of the meter in the Modbus network. Range: 1-2471قراءة/كتابة
ف7-1Baud rate: 0: 1200bps, 1: 2400bps, 2: 4800bps, 3: 9600bps, 4: 19200bps, 5: 38400bps.3قراءة/كتابة
ف7-2Data format: 0: 8N1 (8 data bits, 1 stop bit, no parity), 1: 8E1 (8 data bits, 1 stop bit, even parity), 2: 8O1 (8 data bits, 1 stop bit, odd parity), 3: 8N2 (8 data bits, 2 stop bits, no parity).0قراءة/كتابة
ف7-3Response delay: The delay time before the meter responds to a Modbus query. Used to prevent bus collisions in half-duplex communication. Range: 0-100ms.5قراءة/كتابة
ف7-4Communication type: 0: The display table is in the network host mode, 1: The display table is in the network slave mode, 2: The display table through the broadcast mode.0قراءة/كتابة
ف7-5Parameter interval: The interval time for the meter to send parameters. Range: 0-1000ms.100قراءة/كتابة
ف7-6Send recovery time: The time for the meter to send recovery parameters. Range: 0-1000ms.100قراءة/كتابة
ف7-7Software version number: Displays the current software version.1.00للقراءة فقط

Modbus-RTU Protocol Details:

The meter supports standard Modbus-RTU protocol. The communication parameters (address, baud rate, data format) must be configured correctly to match the master device. The image also shows a table of Modbus register addresses for various parameters (e.g., F0-0, F0-1, F1-0, etc.) which can be read or written via Modbus commands.

For detailed Modbus register addresses and functions, refer to the provided diagram (Figure 5.1) or the official Modbus communication guide for this device. Example: To read F0-0, use Modbus function code 03 (Read Holding Registers) with the corresponding address.

6. الصيانة

  • تنظيف: Use a soft, dry cloth to clean the meter's display and casinز. لا تستخدم المنظفات أو المذيبات الكاشطة.
  • بيئة: Ensure the meter is operated within its specified environmental conditions (temperature, humidity) to prolong its lifespan.
  • الاتصالات: Periodically check all wiring connections for tightness and ensure they are free from corrosion.
  • معايرة: If accuracy issues are suspected, refer to the parameter settings for input offset and gain adjustment, or consult a qualified technician for recalibration.

7. استكشاف الأخطاء وإصلاحها

مشكلةالسبب المحتملحل
العداد لا يعمل.لا يوجد مصدر طاقة أو مستوى صوت غير صحيحtage.Check power connections and ensure voltage is within DC6~25V (or DC8~25V for relay version).
Display shows "----".No analog input signal detected or signal below F1-4 threshold.Verify sensor connection and output. Check F1-4 (Drop detection threshold) setting.
Incorrect readings.Incorrect input type (F1-0), offset (F1-2), or gain (F1-3) settings. Sensor malfunction.Review F1-0, F1-2, F1-3 parameters. Check sensor calibration and output.
فشل الاتصال RS485.Incorrect RS485 parameters (F7-0 to F7-4). Wiring issues.Verify F7-0 (Local address), F7-1 (Baud rate), F7-2 (Data format) match the master device. Check RS485 wiring (R, T, S).

8. المواصفات

ماركةوحدات جودي
نموذجالإصدار القياسي
أنواع إشارة الإدخالالمجلدtage (0-10V, 2-10V), Current (0-20mA, 4-20mA)
Power Supply (Standard/RS485)تيار مستمر 6~25 فولت
Power Consumption (Standard/RS485)24 فولت/40 مللي أمبير
Power Supply (Relay Output Version)تيار مستمر 8~25 فولت
Power Consumption (Relay Output Version)24 فولت/50 مللي أمبير
مقاومة الدخل (Vol)tage Type)> 30 كيلو أوم
Input Impedance (Current Type)<250Ω
عرض0.55 inch, 4-digit digital tube
الحجم الميكانيكي79 × 43 × 25 ملم
افتتاح التثبيت76.5 × 39.5 ملم
وزن50 جرام
RS485 Protocol (Optional)مودبوس-RTU
إخراج التتابع (اختياري)1 Normally Open, 3A30VDC/3A250VAC

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.