Tyenaza ETCR2100A+ Digital Clamp Resistance Tester User Manual

Model: ETCR2100A+

1. المقدمة

This manual provides essential instructions for the safe and effective operation of the Tyenaza ETCR2100A+ Digital Clamp Resistance Tester. This device is designed for accurate measurement of grounding resistance and circuit resistance, featuring a dustproof and shockproof structure for reliable performance in various industrial and departmental settings.

Please read this manual thoroughly before using the instrument to ensure proper handling and to prevent damage or injury.

Tyenaza ETCR2100A+ Digital Clamp اختبار المقاومة

Image 1.1: The Tyenaza ETCR2100A+ Digital Clamp Resistance Tester, showing its overall design with the clamp jaw and control panel.

2. معلومات السلامة

Always observe the following safety precautions to avoid electric shock, injury, or damage to the instrument:

  • لا تستخدم الجهاز إذا بدا تالفًا أو كان يعمل بشكل غير طبيعي.
  • تأكد من إغلاق حجرة البطارية بإحكام قبل التشغيل.
  • لا تحاول قياس الدوائر الكهربائية الحية بما يتجاوز الجهد المحددtage limits (CAT III 150V).
  • Avoid using the instrument in wet environments or during thunderstorms.
  • Refer to qualified personnel for any repairs or servicing.
  • Keep the instrument away from strong magnetic fields and electric fields exceeding specified limits.

3. محتويات العبوة

تأكد من وجود جميع العناصر في العبوة:

  • 1 x ETCR2100A+ Digital Clamp اختبار المقاومة
  • 1 x Accessory (likely a test ring or similar calibration aid)
  • 1 × دليل المستخدم (هذه الوثيقة)
  • 1 × صندوق تخزين

Note: 1.5V AA batteries (x4) are required and are not included in the package.

ETCR2100A+ Digital Clamp Resistance Tester with included accessory

Image 3.1: The ETCR2100A+ tester shown with a standard test ring, which is typically included as an accessory for calibration or verification.

4. مواصفات المنتج

The ETCR2100A+ Digital Clamp Resistance Tester offers the following key features:

  • عرض متعدد الوظائف: Resistance and current values are displayed simultaneously on a new black luxury screen.
  • دقة عالية: Microprocessor-controlled for precise grounding resistance detection, utilizing fast filtering technology to minimize interference.
  • إدارة البيانات: Features real-time clock, data storage for up to 99 sets, and data retrieval capabilities.
  • إنذار صوتي ومرئي: "Beep beep beep" alarm sound with adjustable threshold settings for resistance (1-199 Ω) and current (1-499mA).
  • وظائف تلقائية: Automatic shutdown and fully automatic gear shifting for ease of use.
  • تصميم قوي: Shockproof and dustproof structure, suitable for demanding industrial environments.
  • تطبيق واسع: Ideal for telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, tower transmission lines, gas stations, factory grounding grids, and lightning rod systems.
عن قرب view من clamp jaws of the ETCR2100A+ tester

الصورة 4.1: لقطة مقربة view of the robust clamp jaws, highlighting the double insulation and structural features designed for durability and safety.

5. الإعداد

5.1 تركيب البطارية

The ETCR2100A+ requires four (4) 1.5V AA batteries (not included).

  1. حدد موقع غطاء حجرة البطارية في الجزء الخلفي من الجهاز.
  2. Use a suitable tool (if necessary) to open the battery compartment.
  3. Insert four 1.5V AA batteries, ensuring correct polarity (+/-) as indicated inside the compartment.
  4. أغلق غطاء حجرة البطارية جيدًا.

5.2 التشغيل المبدئي

بعد تركيب البطارية، اضغط على تشغيل/إيقاف button to power on the device. The LCD display will illuminate, indicating the device is ready for use.

6. تعليمات التشغيل

6.1 القياس الأساسي

To perform a grounding resistance test:

  1. تأكد من تشغيل الجهاز.
  2. افتح الكلamp فكّي الفكين بالضغط على الزناد.
  3. ضع الكلamp around the grounding conductor or circuit to be measured. Ensure the jaws are fully closed around the conductor.
  4. The resistance value will be displayed on the LCD screen. The device features fully automatic shifting.
  5. The single measurement time is approximately 0.5 seconds.
ETCR2100A+ tester clamping an insulated ground wire

Image 6.1: The ETCR2100A+ tester shown clamping an insulated ground wire, demonstrating its capability to accurately test even insulated conductors.

6.2 Single Point Grounding System, Auxiliary Measurement

For single point grounding systems where direct clamp measurement of the lead wire is not feasible, auxiliary methods can be used. The two-point method is illustrated below:

Diagram illustrating the two-point auxiliary measurement method for single point grounding systems

Image 6.2: Diagram showing the two-point method for auxiliary grounding resistance measurement. It depicts a grounding rod (RA) connected to a single point, with a wire extending to a natural grounding point (e.g., water pipe, buried metal) for measurement.

لاستخدام هذه الطريقة:

  • Identify a natural grounding point with a low resistance value near the grounding point to be measured. Examples include a water pipe, fire hydrant, or other deeply buried metal structure.
  • Connect a wire from the point to be measured to this auxiliary grounding point.
  • Clamp the ETCR2100A+ around the connecting wire to perform the measurement.
ETCR2100A+ Digital Clamp Resistance Tester in an industrial substation environment

Image 6.3: The ETCR2100A+ tester positioned in an industrial substation, illustrating a typical application environment for grounding resistance measurement.

6.3 تخزين البيانات واسترجاعها

يمكن للجهاز تخزين ما يصل إلى 99 مجموعة من بيانات القياس.

  • To store data: After a measurement, press the ميم button to save the current reading.
  • To retrieve data: Press the ميم button repeatedly to cycle through stored data.

6.4 وظيفة الإنذار

The ETCR2100A+ features an audible and visual alarm for out-of-range measurements.

  • To activate/deactivate the alarm: Press the AL زر.
  • To set alarm thresholds: Refer to the device's on-screen menu or specific instructions for setting resistance (1-199 Ω) and current (1-499mA) alarm limits.
Hand holding the ETCR2100A+ Digital Clamp اختبار المقاومة

Image 6.4: A hand holding the ETCR2100A+ tester, demonstrating its ergonomic design and ease of handling during operation.

7. الصيانة

7.1 التنظيف

Wipe the instrument's exterior with a soft, damp cloth. Do not use abrasive cleaners or solvents. Ensure the device is powered off before cleaning.

7.2 التخزين

When not in use for extended periods, remove the batteries to prevent leakage. Store the instrument in its provided storage box in a cool, dry place, away from direct sunlight and extreme temperatures.

7.3 المعايرة

Regular calibration by qualified personnel is recommended to maintain measurement accuracy, especially after prolonged use or if accuracy is suspected to be compromised.

8. استكشاف الأخطاء وإصلاحها

مشكلةالسبب المحتملحل
الجهاز لا يعمل.البطاريات الميتة أو المثبتة بشكل غير صحيح.استبدل البطاريات ببطاريات AA جديدة بجهد 1.5 فولت، مع التأكد من صحة القطبية.
قراءات غير دقيقة.Jaws not fully closed; interference from external fields; dirty jaws; need for calibration.Ensure jaws are fully closed. Move away from strong magnetic/electric fields. Clean jaws. Consider professional calibration.
أصوات التنبيه بشكل مستمر.Measurement exceeds set alarm threshold.Check the measured value against the set alarm limits. Press the AL button to silence or deactivate the alarm.
العرض فارغ أو وميض.Low battery power; environmental conditions (extreme temperature/humidity).Replace batteries. Operate within specified temperature and humidity ranges (-20 ℃ to 55 ℃; 10% RH to 90% RH).

9. المواصفات

نموذجETCR2100A+
وظيفةGrounding resistance test, circuit resistance test, leakage current test
مدى المقاومة0.01 Ω إلى 200 Ω
دقة المقاومة0.001 أوم
النطاق الحاليNone (for leakage current test, the range is 1-499mA for alarm setting)
تخزين البيانات99 مجموعات
Alarm Threshold Setting Range (Resistance)1-199 أوم
Alarm Threshold Setting Range (Current)1-499 مللي أمبير
درجة حرارة العمل والرطوبة-20 ℃ to 55 ℃; 10% RH to 90% RH
شاشة LCD4 digit LCD digital display
حجم العرضApprox. 47 x 28.5mm / 1.85 x 1.12in (L x W)
Jaw Size (Round)Approx. 32mm / 1.26in diameter
Jaw Opening Size (Long)حوالي 32 مم / 1.26 بوصة
Clamp Size (Long Jaw)تقريبًا 260 × 90 × 56 مم / 10.24 × 3.54 × 2.2 بوصة
مستوى الحمايةعزل مزدوج
السمات الهيكليةClamp shaped CT
تغيير التروسFully automatic shifting
المجال المغناطيسي الخارجي<40A / م
المجال الكهربائي الخارجي<1V / م
وقت القياس الفرديثانيتين
تردد قياس المقاومةGreater than 1KHz
Tested Current Frequency50/60Hz automatic
مزود الطاقة4 بطاريات AA بقوة 1.5 فولت (غير متضمنة)
مادةنظام ABS
وزن العنصر2.13 كيلوجرام / 4.69 جنيه

10. الضمان والدعم

للاستفسار عن الضمان أو الدعم الفني أو خدمات الصيانة، يُرجى التواصل مباشرةً مع بائع التجزئة أو الشركة المصنعة. احتفظ بإيصال الشراء كإثبات للشراء.

Manufacturer: Tyenaza

© 2023 Tyenaza. All rights reserved.